Epsilon EP-P Drive and FM-3/4 Module Reference Manual
Fault Codes
A number of diagnostic and fault detection circuits are incorporated to protect the drive. Some faults, such as High DC Bus
and Motor Over Temperature can be reset with the Reset button on the front of the drive or the Reset input function. Other
faults, such as Encoder Faults, can only be reset by cycling power “Off” (wait until the diagnostics display turns “Off”), then
power “On”.
The drive accurately tracks motor position during fault conditions. For example, if there is a Low DC Bus fault where the
power stage is disabled, the drive will continue to track the motor’s position provided the logic power is not interrupted.
The +/- Travel Limit faults are automatically cleared when the fault condition is removed.
Program Program is executing.
Drive Type Address
Motor Type
Menu Groups
Pulse Mode Pulse Mode Operation is executing. NA
Torque Mode Analog Torque Mode Operation NA
Velocity Mode Analog Velocity Mode Operation NA
Segment Display Fault Action to Reset Bridge Disabled
FM-3/4 Keypad Display
(When Applicable)
Flash Invalid Reprogram the Flash Yes
Drive or Module
Power Up Test
Cycle Logic Power Yes
DV PwrUp
or
FmPwrUp
Drive or Module
NVM Invalid
Reset Button or Input Line Yes
DvInvNVM
or
FmInvNVM
Invalid Configuration Reset Button or Input Line Yes Inv Cfg
Power Module Reset Button or Input Line Yes DvPwr Mod
High DC Bus Reset Button or Input Line Yes Hi Bus
Low DC Bus Reset Button or Input Line Yes Low Bus