
168
Epsilon EP-P Drive and FM-3/4 Module Reference Manual
Figure 106: Home Setup View
Deceleration - Is the average deceleration rate used to decelerate from the target velocity to zero velocity at the completion
of the home.
Home Offset – By selecting a specified offset, the home will travel at a set velocity until the home reference signal is detected,
then travel an additional set distance, before coming to a stop. The deceleration ramp begins at the proper time, to ensure the
home completes precisely at the specified offset distance after the home reference was detected. In order to decelerate to a
stop immediately upon detecting the home reference, select the “Calculated Offset” radio box.
Limit Distance – Is the maximum incremental distance the home move will travel without seeing a home reference signal.
If the home move does travel this distance without seeing a home reference, it will come to a stop exactly at this point, and
the Home.0.LimitDistHit source will activate. If the box is left unchecked, the home move will continue without limit, until
a home reference is seen.
Index Setup
Next, setup any indexes required by your application. Select one of the indexes from the Hierarchy Tree. Figure 107 shows
Index0.
Comentarios a estos manuales