Vission 20/20 Retrofit Instructions
Vista de pagina 0
1 2 3 4 5 6 ... 13 14

Indice de contenidos

Pagina 1

Vission 20/20 Retrofit Instructions

Pagina 2

10ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 2. An auxiliary contact from compressor motor starter is required. Connect isolated contact t

Pagina 3 - 1.0 General Information

11ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 4. A dry contact from control relay CR12 must be wired to oil pump motor starter coil. This d

Pagina 4 - 2.1 Removal

12ViSSion® 20/20 Retrofi t Instructions • 35391SCRFTorque Specifications (ft-lbs)TypeBoltHeadMarkingsNominal Size Numbers or Inches#10 1/4 5/16 3/8 7/1

Pagina 6

35391SCRF Rev. 1 (4/13) Emerson and Vilter are trademarks of Emerson Electric Co. or one of its affi liated companies. © 2012 Emerson Climate Technolog

Pagina 8

3ViSSion® 20/20 Retrofi t Instructions • 35391SCRFTable of ContentsSections Page1.0 General Information ...

Pagina 9

4ViSSion® 20/20 Retrofi t Instructions • 35391SCRF2.0 Vission 20/20 Retrofi t Instructions This procedure defi nes the steps required to replace a Vilt

Pagina 10 - #12AWG THHN (MINIMUM)

5ViSSion® 20/20 Retrofi t Instructions • 35391SCRF2.2 InstallationNOTETorque all hardware according to torque table specifi cations, see Table 1.NOTEMod

Pagina 11 - CUSTOMER ANALOG WIRING

6ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 8. Install hardware to secure new vibration isolators (5) to mounting holes of Vission 20/20 mi

Pagina 12

7ViSSion® 20/20 Retrofi t Instructions • 35391SCRFNOTEStainless steel tubing is not provided in a retrofi t kit.Step 10. Route stainless steel tubing f

Pagina 13

8ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 12. Connect cables (10) to transducers (7).Figure 6. Block and Bleed Assembly with Transduce

Pagina 14

9ViSSion® 20/20 Retrofi t Instructions • 35391SCRFCAUTIONDo not route A/C and D/C wires together, this willcause Electromagnetic Interferance. Failure