3B
UPS Systems
91
Table 45 Liebert SICE 7200 - Input and Holding Registers - SSC
Controller
System Control Cabinet - SSC
Liebert Products
Liebert SICE 7200
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Bypass Overtemperature
-
40290
1
-
Bit 3
Inverter Non Sync
-
40290
1
-
Bit 4
Output Overvoltage
-
40290
1
-
Bit 5
Output Undervoltage
-
40290
1
-
Bit 6
Output Undervoltage
-
40290
1
-
Bit 7
Output Waveform Error
-
40290
1
-
Bit 8
Transfer Count Block
-
40290
1
-
Bit 9
Overload Shutdown
-
40290
1
-
Bit 10
Overtemperature Shutdown
-
40291
1
-
Bit 0
Emergency Stop
-
40291
1
-
Bit 1
Overload Present
-
40291
1
-
Bit 2
Overload Shutdown TO
-
40291
1
-
Bit 3
Display Error
-
40291
1
-
Bit 4
Display Error
-
40291
1
-
Bit 5
Invewrter Over Capacity
-
40291
1
-
Bit 6
Parallel Bus Open
-
40291
1
-
Bit 7
Battery Ground Fault
-
40291
1
-
Bit 8
Bypass Backfeed
-
40291
1
-
Bit 9
Bypass Sync Inhibited
-
40291
1
-
Bit 10
Bypass ECO Mode
-
40291
1
-
Bit 11
Fan Failure
-
40291
1
-
Bit 12
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.