Emerson Liebert FPC Manual de usuario Pagina 94

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 93
3B
UPS Systems
90
Table 45 Liebert SICE 7200 - Input and Holding Registers - SSC
Controller
System Control Cabinet - SSC
Liebert Products
Liebert SICE 7200
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Output Voltage L1-L2
-
40001
1
-
V
Output Voltage L2-L3
-
40002
1
-
V
Output Voltage L3-L1
-
40003
1
-
V
Output Amps L1
-
40004
1
-
A
Output Amps L2
-
40005
1
-
A
Output Amps L3
-
40006
1
-
A
Power L1
-
40007
1
-
kW
Power L2
-
40008
1
-
kW
Power L3
-
40009
1
-
kW
Bypass Frequency
-
40010 1
10
Hz
Battery Voltage
-
40012
1
-
V
Battery Amperage
-
40013
1
-
A
Apparent Power L1
-
40014
1
-
kVA
Apparent Power L2
-
40015
1
-
kVA
Apparent Power L3
-
40016
1
-
kVA
% Load L1
-
40017
1
-
%
% Load L2
-
40018
1
-
%
% Load L3
-
40019
1
-
%
% Battery Charge
-
40020
1
-
%
Battery Temperature
-
40021
1
-
deg C
Battery Time Remaining
-
40022
1
-
Minutes
Communications
-
40289
1
-
Bit 0
Bypass Switch Open
-
40289
1
-
Bit 1
Output Switch Open
-
40289
1
-
Bit 2
Battery CB Open
-
40289
1
-
Bit 3
Manual Bypass Closed
-
40289
1
-
Bit 4
Bypass Absent
-
40289
1
-
Bit 5
Bypass Overvoltage
-
40289
1
-
Bit 6
Bypass Undervoltage
-
40289
1
-
Bit 7
Bypass Frequency Error
-
40289 1
-
Bit 8
Bypass Ph Rotation Error
-
40289
1
-
Bit 9
Bypass SCR Failure
-
40289
1
-
Bit 10
Bypass Off
-
40290
1
-
Bit 0
Bypass Off
-
40290
1
-
Bit 1
Load On Bypass
-
40290
1
-
Bit 2