3B
UPS Systems
84
Table 42 Liebert Series 300
UPS - Status and Coil
Data Point
Status
Coil
Number of Bits
Notes / Units
Automatic Restart Enabled
10001
1
1
-
Battery Charge Compensation 10046 - 1 -
Inverter Ready
10047
-
1
-
Load Circuit 1 State
10057
-
1
-
Load Circuit 2 State
10058
-
1
-
Load Circuit 3 State
10059
-
1
-
Load Circuit 4 State
10060
-
1
-
Load Circuit 5 State
10061
-
1
-
Load Circuit 6 State
10062
-
1
-
Load Circuit 7 State
10063
-
1
-
Load Circuit 8 State
10064
-
1
-
Load Circuit 9 State
10065
-
1
-
Load Circuit 10 State
10066
-
1
-
Load Circuit 11 State
10067
-
1
-
Load Circuit 12 State
10068
-
1
-
Load Circuit 13 State
10069
-
1
-
Load Circuit 14 State
10070
-
1
-
Load Circuit 15 State
10071
-
1
-
Load Circuit 16 State
10072
-
1
-
Load On Inverter
10073
-
1
-
Bypass Active
10074
-
1
-
Buck On
10076
-
1
-
Replace Battery
10081
-
1
-
Battery Under Test
10082
-
1
-
Load On Battery
10128
-
1
-
Low Battery - Shutdown Imminent
10152
-
1
-
Output Overload
10154
-
1
-
Over Temperature Warning
10171
-
1
-
Battery Over Temperature CB Trip
10172
-
1
-
Input Power Supply Fail
10186
-
1
-
Input Over Voltage
10187
-
1
-
Input Under Voltage
10188
-
1
-
Bad Input Frequency
10190
-
1
-
Bypass Input Voltage/Frequency
Fault
10202 - 1 -
Output Under Voltage
10218
-
1
-
Output Over Voltage
10219
-
1
-
Battery Charger Fail
10234
-
1
-