Vista de pagina 29
1B
Precision Cooling Products
26
Table 14 Liebert Challenger 3000
, Liebert Deluxe System/3
, Liebert ICS
, Liebert Himod
-
Input and Holding Registers - LAM
Controller
Advanced Microprocessor - LAM
Liebert Products
Liebert Challenger 3000
Liebert Deluxe System/3
Liebert ICS
Liebert Himod (LNA version - Using Sitescan)
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Status Points (View)
Temperature
-
40001
1
-
-
Humidity
-
40002
1
-
-
Cooling
-
40003
1
-
1=On / 0=Off
Heating
-
40004
1
-
1=On / 0=Off
Humidification
-
40005
1
-
1=On / 0=Off
De-humidification
-
40006
1
-
1=On / 0=Off
Econ-O-Cycle
-
40007
1
-
1=On / 0=Off
Stages
-
40008
1
-
-
% Capacity
-
40009
1
-
-
Unit Status (On / Off)
-
40018
1
-
1=On / 0=Off (R/W)
Analog input 1
- 40023 1
-
A/D raw value w/ slope
=1 and offset = 0
Analog input 2
- 40024 1
-
A/D raw value w/ slope
=1 and offset = 0
Analog input 3
- 40025 1
-
A/D raw value w/ slope
=1 and offset = 0
Analog input 4
- 40026 1
-
A/D raw value w/ slope
=1 and offset = 0
Alarm Points
Discrete alarm objects
available; use auto-
discover for this unit
Communications
-
40289
1
-
Bit 0
Local Off
-
40289
1
-
Bit 1
Remote Off
- 40289 1
-
Bit 2
High Head Pressure 1
-
40289
1
-
Bit 3
High Head Pressure 2
-
40289
1
-
Bit 4
Loss of Airflow
-
40289
1
-
Bit 5
Standby Glycol Unit On
-
40289
1
-
Bit 6
Liquid Detected
-
40289
1
-
Bit 7
Change Filters
-
40289
1
-
Bit 8
High Temperature
-
40289
1
-
Bit 9
Low Temperature
-
40289
1
-
Bit 10
High Humidity
-
40290
1
-
Bit 0
Vista de pagina 29