Emerson Liebert FPC Manual de usuario Pagina 38

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 37
1B
Precision Cooling Products
34
Table 17 Liebert Mini-Mate 8 Ton - Input and Holding Registers - L8T
Controller
L8T
Liebert Products
Liebert Mini-Mate 8 Ton
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Temperature Setpoint
-
40350
1
-
(W)
Temperature Tolerance
-
40350
1
1000
(W)
Humidity Setpoint
-
40351
1
-
(W)
Humidity Tolerance
-
40351
1
1000
(W)
Reheat Lockout
-
40349 1
-
Bit 2 On=RH Off
Bit 3 On=RH On
Humidifier Lockout
-
40349 1
-
Bit 4 On=HL Off
Bit 5 On=HL On
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.
Vista de pagina 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 99 100