Emerson Liebert FPC Manual de usuario Pagina 21

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 20
1B
Precision Cooling Products
17
Table 9 Liebert DS and Liebert PEX - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Note
Humidifier Run Hours Threshold
30073
40073
-
-
Hours
Dehumidification Run Hours Threshold
30074
40074
-
-
Hours
CW/FC Run Hours Threshold
30075
40075
-
-
Hours
Electrical Heaters #1 Run Hours
Threshold
30076 40076
-
- Hours
Electrical Heaters #2 Run Hours
Threshold
30077 40077
-
- Hours
Electrical Heaters #3 Run Hours
Threshold
30078 40078
-
- Hours
Hot Water / Hot Gas Run Hours
Threshold
30079 40079
-
- Hours
Operating State
6
30100
-
-
-
-
Number of Active Events/Alarm
30101
-
-
-
-
Summary Alarm Status
7
30102
-
-
-
-
Fan Ramp
30103
-
-
-
%
Cooling Ramp
30104
-
-
-
%
Free Cooling Ramp
30105
-
-
-
%
Heating Ramp
30106
-
-
-
%
Humidification Ramp
30107
-
-
-
%
Dehumidifier Ramp
30108
-
-
-
%
FreeCooling Status
8
30109
-
-
-
%
Return Temperature
30110
-
-
10
deg C
Actual Temperature SP
30111
-
-
10
deg C
Supply Temperature
30112
-
-
10
deg C
Actual Supply Temperature SP
30113
-
-
10
deg C
FC Temperature
30115
-
-
10
deg C
Sensor A Temperature
30116
-
-
10
deg C
Sensor B Temperature
30117
-
-
10
deg C
Sensor C Temperature
30118
-
-
10
deg C
Digital Scroll Compressor 1 High
Temperature
30119 -
-
10 deg C
Digital Scroll Compressor 2 High
Temperature
30120 -
-
10 deg C
Return Humidity
30130
-
-
-
%
Actual Humidity SP
30131
-
-
-
%
Sensor A Humidity
30132
-
-
-
%
Sensor B Humidity
30133
-
-
-
%
Sensor C Humidity
30134
-
-
-
%
Fan Run Hour
30141
-
-
-
Hours
Compressor 1 Run Hour
30142
-
-
-
Hours
Compressor 2 Run Hour
30143
-
-
-
Hours
Vista de pagina 20