Table 17 Liebert Mini-Mate 8 Ton - Input and Holding Registers - L8T
Controller
L8T
Liebert Products
Liebert Mini-Mate 8 Ton
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Not Used
-
40291
1
-
Bit 0
Short Cycle
-
40291
1
-
Bit 1
Loss of Power
-
40291
1
-
Bit 2
Local Alarm 1
-
40291
1
-
Bit 6
Local Alarm 2
-
40291
1
-
Bit 7
EPO Shutdown
-
40291
1
-
Bit 8
Local Alarm 3
-
43291
1
-
Bit 9
Local Alarm 4
-
40291
1
-
Bit 10
Run Times (View)
Compressor 1 Run Hours
-
40019
1
-
-
Compressor 2 Run Hours
-
40020
1
-
-
Glycol Run Hours
-
1
-
-
Fan Motor Run Hours
-
40021
1
-
-
Humidifier Run Hours
-
40022
1
-
-
Reheat 1 Run Hours
-
1
-
-
Reheat 2 Run Hours
-
1
-
-
Reheat 3 Run Hours
-
1
-
-
Chilled H2O Valve Run Hours
-
1
-
-
Setpoints (View)
Temperature Setpoint
-
40010 1
-
(R/W)
Temperature Tolerance
-
40011
1
-
(R/W)
Humidity Setpoint
-
40012
1
-
(R/W)
Humidity Tolerance
-
40013
1
-
(R/W)
High Temperature Alarm Setpoint
-
40014
1
-
(R/W)
Low Temp Alarm Setpoint
-
40015
1
-
(R/W)
High Humidity Alarm Setpoint
-
40016
1
-
(R/W)
Low Humidity Alarm Setpoint
-
40017
1
-
(R/W)
Winter Start Delay
-
40028
1
-
Minutes (R/W)
Auto Flush Rate
-
40029
1
-
% (R/W)
Chill Water Flush Rate
-
40030
1
-
Hours (R/W)
Auto Restart Delay
-
40031
1
-
0.1 minute (R/W)
Control Points (Set)
-
Unit Status (On / Off)
-
40018
1
-
1=On / 0=Off (R/W)
Unit On / Off
-
40349 1
-
Bit 0 On=unit Off
Bit 1 On=unit On (W)