3B
UPS Systems
53
Table 26 Liebert NX
- Status and Coil
Data Point
Status
Coil
Number
of Bits
Scale
Notes / Units
Battery Fault
10235
-
-
-
-
Battery Contact Fail
10236
-
-
-
-
Battery Converter Over Current
10237
-
-
-
-
Battery Converter Fail
10238
-
-
-
-
DC Bus Balancer Over Current
10239
-
-
-
-
DC Bus Balancer Fault
10240
-
-
-
-
DC Bus 1 Power Supply Fail
10251
-
-
-
-
Rectifier Fuse Fail
10257
-
-
-
-
Rectifier Startup Failure
10258
-
-
-
-
Rectifier Fault
10259
-
-
-
-
Rectifier Current Limit
10260
-
-
-
-
Inverter DC Voltage Low Shutdown
10262
-
-
-
-
Inverter Fault
10263
-
-
-
-
Inverter DC Offset Overload
10264
-
-
-
-
Inverter Contactor Fail
10265
-
-
-
-
Inverter Current Limit
10266
-
-
-
-
Parallel Low Battery Warning
10267
-
-
-
-
Load Share Fault
10268
-
-
-
-
Parallel System Fault
10269
-
-
-
-
Parallel Connection Error
10270
-
-
-
-
Parallel System Overload
10271
-
-
-
-
Parallel Transfer To Static Bypass
Switch
10272 - - - -
Inverter Communication Fail
10281
-
-
-
-
Rectifier Communication Failure
10282
-
-
-
-
Parallel Communication Fault
10283
-
-
-
-
Operation Fault
10289
-
-
-
-
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.