3B
UPS Systems
71
Table 33 Liebert PowerSure Interactive 2 - Input and Holding Registers
Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153)
Load Circuit Present 30013 40013 1 -
There are 16 possible Load
Circuits. Each bit
represents 1 load circuit.
Load Circuit 1 is bit 0, Load
Circuit 2 is bit 1 and so on. If
the bit is 1, then the Load
-
Nominal Battery Float Voltage
Ambient Temperature Warning Point
Over Temperature Limit Point
Battery Charge Status 30112 - 1 -
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
Battery Charge Percentage