3B
UPS Systems
76
Table 35 Liebert GXT2 - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Battery Test Result 30130 - 1 -
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1
30153
-
1
-
V
Bypass Voltage L1
30159
-
1
-
V
Output Voltage L1
30163
-
1
-
V
Output Current L1
30164
-
1
-
A
Input Maximum Voltage L1
30180
-
1
-
V
Input Minimum Voltage L1
30181
-
1
-
V
Output Maximum Voltage L1
30182
-
1
-
V
Output Minimum Voltage L1
30183
-
1
-
V
Black Out Count
30301
-
1
-
-
Brown Out Count
30302
-
1
-
-
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.