Precision Cooling Products
24
Table 13 Liebert XDP with Liebert iCOM - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Pump 1 State
30385
-
1
-
0=Off / 1=On
Pump 2 State
30386
-
1
-
0=Off / 1=On
Supply Refrigerant Temperature
30387
-
1
0.1
deg C
Supply Refrigerant Temperature
30388
-
1
0.1
deg F
Supply Chilled Water
Temperature
30389
-
1 0.1 deg C
Supply Chilled Water
Temperature
30390
-
1 0.1 deg F
System Status
30391
-
1
-
1=Normal Operation
2=Startup
8=Normal with Warning
16=Normal with Alarm
32=Abnormal Operation
System Operating State
30392
-
1
-
0=Off / 1=On
2=Standby
Ext Air Sensor A Temperature
30393
-
1
0.1
deg C
Ext Air Sensor A Temperature
30394
-
1
0.1
deg F
Ext Air Sensor A Humidity
30395
-
1
0.1
% RH
Ext Air Sensor A Dew Point
Temp
30396
-
1 0.1 deg C
Ext Air Sensor A Dew Point
Temp
30397
-
1 0.1 deg F
Ext Air Sensor B Temperature
30398
-
1
0.1
deg C
Ext Air Sensor B Temperature
30399
-
1
0.1
deg F
Ext Air Sensor B Humidity
30400
-
1
0.1
% RH
Ext Air Sensor B Dew Point
Temp
30401
-
1 0.1 deg C
Ext Air Sensor B Dew Point
Temp
30402
-
1 0.1 deg F
Minimum Room Temperature
Set Point
30403 40403 1 - deg C
Minimum Room Temperature
Set Point
30404 40404 1 - deg F
Ext Air Over Temp Threshold
30405
40405
1
-
deg C
Ext Air Over Temp Threshold
30406
40406
1
-
deg F
Ext Air Under Temp Threshold
30407
40407
1
-
deg C
Ext Air Under Temp Threshold
30408
40408
1
-
deg F
Ext Dew Point Over Temp
Threshold
30409 40409 1 - deg C
Ext Dew Point Over Temp
Threshold
30410 40410 1 - deg F
Supply Refrig Over Temp
Threshold
30411 40411 1 - deg C
Supply Refrig Over Temp
Threshold
30412 40412 1 - deg F