1B
Precision Cooling Products
24
Table 13 Liebert XDP with Liebert iCOM - Input and Holding Registers
Pump 1 State
-
-
Supply Refrigerant Temperature
Supply Refrigerant Temperature
Supply Chilled Water
Temperature
30389
-
1 0.1 deg C
Supply Chilled Water
30390
-
1 0.1 deg F
System Status
30391
-
1
-
2=Startup
8=Normal with Warning
16=Normal with Alarm
System Operating State
30392
-
1
-
Ext Air Sensor A Temperature
Ext Air Sensor A Temperature
Ext Air Sensor A Humidity
Ext Air Sensor A Dew Point
Temp
30396
-
1 0.1 deg C
Ext Air Sensor A Dew Point
Temp
30397
-
1 0.1 deg F
Ext Air Sensor B Temperature
Ext Air Sensor B Temperature
Ext Air Sensor B Humidity
Ext Air Sensor B Dew Point
30401
-
1 0.1 deg C
Ext Air Sensor B Dew Point
Temp
30402
-
1 0.1 deg F
Minimum Room Temperature
Set Point
30403 40403 1 - deg C
Minimum Room Temperature
30404 40404 1 - deg F
Ext Air Over Temp Threshold
Ext Air Over Temp Threshold
Ext Air Under Temp Threshold
Ext Air Under Temp Threshold
Ext Dew Point Over Temp
30409 40409 1 - deg C
Ext Dew Point Over Temp
Threshold
30410 40410 1 - deg F
Threshold
30411 40411 1 - deg C
Supply Refrig Over Temp
Threshold
30412 40412 1 - deg F