3B
UPS Systems
49
4.0 UPS SYSTEMS
Table 24 Liebert Nfinity
®
- Status and Coil
Data Point
Status
Coil
Number of Bits
Notes/Units
Automatic Battery Test Enabled
10003
3
1
-
Battery Charger On
10044
-
1
-
Inverter Ready
10047
-
1
-
Power Factor Correction State
10050
-
1
-
Load on Inverter
10073
-
1
-
Bypass Active
10074
-
1
-
Replace Battery
10081
-
1
-
Battery Under Test
10082
-
1
-
Load on Battery
10128
-
1
-
Load on Bypass
10129
-
1
-
Load on Manual Bypass
10132
-
1
-
Load Transferred to Bypass
Due to UPS Fault
10134 - 1 -
Transfer Inhibit
10146
-
1
-
Output Off Pending
10151
-
1
-
Low Battery - Shutdown Imminent
10152
-
1
-
Output Overload
10154
-
1
-
UPS Overload
10155
-
1
-
Output Off
10158
-
1
-
Check Air Filter - Replace
10170
-
1
-
Transformer Over Temperature
10178
-
1
-
Input Power Supply Fail
10186
-
1
-
Internal Device Communication Failure
10284
-
1
-
Device Active Alarm
10290
-
1
-
Main Control Warning
10291
-
1
-
Redundant Control Warning
10292
-
1
-
Control Module Failure
10293
-
1
-
Redundant Control Module Failed
10294
-
1
-
User Interface Module Failed
10295
-
1
-
UPS Power Not Redundant
10296
-
1
-
Power Module Failure
10298
-
1
-
Battery Module Failure
10299
-
1
-
Power Module Warning
10300
-
1
-
Battery Module Warning
10301
-
1
-