Emerson Liebert FPC Manual de usuario Pagina 92

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 91
3B
UPS Systems
88
Table 44 Liebert SICE 7200
, Liebert HiPulse
- Input and Holding Registers - SMM/SSM
Controller
Multi Module Series - SMM
Liebert Products
Liebert SICE 7200
Liebert HiPulse
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Byp Phase Rotation Error
-
40289
1
-
Bit 10
Bypass SCR Failure
-
40290
1
-
Bit 0
Bypass Off
-
40290
1
-
Bit 1
Bypass Off
-
40290
1
-
Bit 2
Load On Bypass
-
40290
1
-
Bit 3
Bypass Overtemperature
-
40290
1
-
Bit 4
Rectifier Under Voltage
-
40290
1
-
Bit 5
Rectifier Block
-
40290
1
-
Bit 6
Rectifier Block
-
40290
1
-
Bit 7
Rectifier Current Limit
-
40290
1
-
Bit 8
Rectifier Overtemperature
-
40290
1
-
Bit 9
Rectifier Fuse Failure
-
40290
1
-
Bit 10
Inverter Voltage Fault
-
40291
1
-
Bit 0
Inverter Disable
-
40291
1
-
Bit 1
Inverter Disable
-
40291
1
-
Bit 2
Inverter Current Limit
-
40291
1
-
Bit 3
Inverter Overtemperature
-
40291
1
-
Bit 4
Inverter Non Sync
-
40291
1
-
Bit 5
Inverter Overvoltage
-
40291
1
-
Bit 6
Inverter Undervoltage
-
40291
1
-
Bit 7
Inverter Fuse Failure
-
40291
1
-
Bit 8
Output Overvoltage
-
40291
1
-
Bit 9
Output Undervoltage
-
40291
1
-
Bit 10
Output Undervoltage
-
40292
1
-
Bit 0
Output Waveform Error
-
40292
1
-
Bit 1
Inverter Frequency Error
-
40292
1
-
Bit 2
Inverter Parallel Error
-
40292
1
-
Bit 3
Contactor Failure
-
40292
1
-
Bit 4
Battery Test
-
40292
1
-
Bit 5
Battery Test Failed
-
40292
1
-
Bit 6
Battery On Load
-
40292
1
-
Bit 7
Battery End of Discharge
-
40292
1
-
Bit 8
Boost Time Expired
-
40292
1
-
Bit 9
Vista de pagina 91