Emerson Liebert FPC Manual de usuario Pagina 45

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 44
2B
Power Distribution and Power Conditioning Products
41
Table 21 Liebert Datawave, Liebert FPC, Liebert PPC Precision Power Center - Input and
Holding Registers - PMP Option for Liebert FPC and Liebert PPC
Controller
Power Monitoring Panel - PMP
Option for Liebert FPC and Liebert PPC
Liebert Products
Liebert Datawave
Liebert FPC
Liebert PPC
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Status Points (View)
Voltage In X-Y
-
40001
1
-
V
Voltage In Y-Z
-
40002
1
-
V
Voltage In Z-X
-
40003
1
-
V
Voltage Out A-B
-
40004
1
-
V
Voltage Out B-C
-
40005
1
-
V
Voltage Out C-A
-
40006
1
-
V
Voltage Out A-N
-
40007
1
-
V
Voltage Out B-N
-
40008
1
-
V
Voltage Out C-N
-
40009
1
-
V
Current Out A
-
40010
1
-
A
Current Out B
-
40011
1
- A
Current Out C
-
40012
1
-
A
Ground Current
-
40013
1
10
A
Neutral Current
-
40014
1
-
A
kVA
-
40015
1
-
kVA
kW
-
40016
1
-
kW
Frequency
-
40017
1
10
Hz
% Capacity A
-
40018
1
-
%
% Capacity B
-
40019
1
-
%
% Capacity C
-
40020
1
-
%
Alarm Points
Discrete alarm objects
available; use auto-
discover for this unit
Communications
-
40289
1
-
Bit 0
Output Undervoltage
-
40289
1
-
Bit 1
Output Overvoltage
-
40289
1
-
Bit 2
Output Overcurrent
-
40289
1
-
Bit 3
Frequency Deviation
-
40289
1
-
Bit 4
Ground Overcurrent
-
40289
1
-
Bit 5
Transformer Overtemp
-
40289
1
-
Bit 6
Ground Fault
-
40289
1
- Bit 7
Ground Failure
-
40289
1
-
Bit 8
Vista de pagina 44