Emerson Liebert FPC Manual de usuario Pagina 25

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 24
1B
Precision Cooling Products
21
Table 11 Liebert XDF - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Note
Vendor ID
30001
40001
1
-
-
Device ID
30002
40002
1
-
-
Version number
30003
40003
1
-
-
UPS/Env/Pwr
30004
40004
1
-
-
Temperature Setpoint
30023
40023
1
10
deg C
Delay after safe Temp has been
reached
30034 40034
- -
Minutes
Allowable deviation between internal
temp sensors
30035 40035
- -
deg C
High Cabinet Temperature Setpoint
30058
40058
-
10
deg C
Low Cabinet Temperature Setpoint
30059
40059
-
10
deg C
Fan Run Hour Threshold
30070
40070
-
-
Hours
Compressor 1 Run Hour Threshold
30071
40071
-
-
Hours
Service Ramp
30099
-
-
-
%
Operating State
6
30100
-
-
-
-
Number of Active Events/Alarm
30101
-
-
-
-
Summary Alarm Status
7
30102
-
-
-
-
Fan Ramp
30103
-
-
-
%
Cooling Ramp
30104
-
-
-
%
Digital Scroll Compressor 1
High Temperature
30119
- -
10 deg C
Sensor 1 Temp
30121
-
-
10
deg C
Sensor 2 Temp
30122
-
-
10
deg C
Sensor 3 Temp
30123
-
-
10
deg C
Sensor 4 Temp
30124
-
-
10
deg C
Ambient Temp
30125
-
-
10
deg C
Ambient Humidity
30126
-
-
-
%
Dew Point Temp
30127
-
-
-
deg C
Adjusted Setpoint Temp
30128
-
-
10
deg C
Cabinet Temperature
30129
-
-
10
deg C
Service Due Year
30135
-
-
-
-
Service Due Month
30136
-
-
-
-
Device kW Load
30137
-
-
-
kW
Fan Run Hour
30141
-
-
-
Hours
Compressor 1 Run Hour
30142
-
-
-
Hours
Vista de pagina 24