Emerson Liebert FPC Manual de usuario Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
1B
Precision Cooling Products
16
Table 9 Liebert DS and Liebert PEX - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Note
Vendor ID
30001
40001
1
-
-
Device ID
30002
40002
1
-
-
Version Number
30003
40003
1
-
-
UPS/Env/Pwr
30004
40004
1
-
-
Timer Mode
1
30016
40016
1
-
-
Type of DT Room-FC
2
30017
40017
1
-
-
Humidity Control
3
30018
40018
1
-
-
VSD Setpoint
30019
40019
1
-
% (HP)
Supply Temperature Limit
30020
40020
1
10
deg C
DT between Room and FC
30021
40021
1
10
deg C
Minimum CW Temperature
30022
40022
1
10
deg C
Temperature Setpoint
30023
40023
1
10
deg C
Temperature Proportional Band
30024
40024
1
10
deg C
Temperature Deadband
30025
40025
1
10
deg C
Temperature Integration Time
30026
40026
1
-
Minutes
Humidity Setpoint
30027
40027
1
-
%
Humidity Proportional Band
30028
40028
1
-
%
Humidity Integration Time
30029
40029
1
-
Minutes
Humidity Deadband
30030
40030
1
-
%
Single Unit Auto-Restart Delay
30031
40031
1
-
Seconds
Infrared Flush Rate
30032
40032
1
-
%
Temp Control Type
4
30033
40033
1
-
-
Sleep Interval 1 Start Time Hour: Minute
30040
40040
1
-
LSB:Min
Sleep Interval 1 End Time Hour: Minute
30041
40041
1
-
LSB:Min
Sleep Interval 2 Start Time Hour: Minute
30042
40042
1
-
LSB:Min
Sleep Interval 2 End Time Hour: Minute
30043
40043
1
-
LSB:Min
Timer Deadband
30044
40044
1
10
deg C
Manual VSD Timer/Counter
5
30045 40045 1
-
-
High Temperature
30050
40050
1
10
deg C
Low Temperature
30051
40051
1
10
deg C
High Temperature Sensor A
30052
40052
1
10
deg C
Low Temperature Sensor A
30053
40053
1
10
deg C
High Humidity
30054
40054
1
-
%
Low Humidity
30055
40055
1
-
%
High Humidity Sensor A
30056
40056
1
-
%
Low Humidity Sensor A
30057
40057
1
-
%
Fan Run Hour Threshold
30070
40070
-
-
Hours
Compressor 1 Run Hour Threshold
30071
40071
-
-
Hours
Compressor 2 Run Hour Threshold 30072 40072
-
- Hours
Vista de pagina 19