UPS Systems
66
Table 30 Liebert PowerSure
Interactive - Status and Coil
Data Point
Status
Coil
Number of Bits
Notes/Units
Audible Alarm Enabled
10002
2
1
-
Automatic Battery Test Enabled
10003
3
1
-
Battery Charge Compensation
10046
-
1
-
Inverter Ready
10047
-
1
-
Load Circuit 1 State
10057
-
1
-
Load Circuit 2 State
10058
-
1
-
Load Circuit 3 State
10059
-
1
-
Load Circuit 4 State
10060
-
1
-
Load Circuit 5 State
10061
-
1
-
Load Circuit 6 State
10062
-
1
-
Load Circuit 7 State
10063
-
1
-
Load Circuit 8 State
10064
-
1
-
Load Circuit 9 State
10065
-
1
-
Load Circuit 10 State
10066
-
1
-
Load Circuit 11 State
10067
-
1
-
Load Circuit 12 State
10068
-
1
-
Load Circuit 13 State
10069
-
1
-
Load Circuit 14 State
10070
-
1
-
Load Circuit 15 State
10071
-
1
-
Load Circuit 16 State
10072
-
1
-
Load On Inverter
10073
-
1
-
Boost Mode On
10075
-
1
-
Buck Mode On
10076
-
1
-
Battery Under Test
10082
-
1
-
Shutdown Reason - Over Temperature
10086
-
1
-
Shutdown Reason - Overload
10087
-
1
-
Shutdown - Output Short
10089
-
1
-
Shutdown Reason - Remote Shutdown
10093
-
1
-
Load On Battery
10128
-
1
-
Output Off Pending
10151
-
1
-
Low Battery - Shutdown Imminent
10152
-
1
-
Output Overload
10154
-
1
-
Over Temperature Warning
10171
-
1
-
Battery Over Temperature CB Trip
10172
-
1
-
Input Power Supply Fail
10186
-
1
-
Input Over Voltage
10187
-
1
-
Input Under Voltage
10188
-
1
-
Bad Input Frequency
10190
-
1
-
Output Under Voltage
10218
-
1
-
Output Over Voltage
10219
-
1
-