Emerson Liebert FPC Manual de usuario Pagina 34

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 33
1B
Precision Cooling Products
30
Table 16 Liebert Mini-Mate 2, Liebert DataMate - Input and Holding Registers - MM2
Controller
MM2
Liebert Products
Liebert Mini-Mate 2
Liebert DataMate
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Status Points (View)
Temperature
-
40001
1
-
-
Humidity
-
40002
1
-
-
Cooling
-
40003
1
-
1=On / 0=Off
Heating
-
40004
1
-
1=On / 0=Off
Humidification
-
40005
1
-
1=On / 0=Off
Dehumidification
-
40006
1
-
1=On / 0=Off
Econ-o-Cycle
-
40007
1
-
1=On / 0=Off
Stages
- 40008 1
-
-
% Capacity
-
40009
1
-
-
Alarm Points
Communications
-
40289
1
-
Bit 0
Local Off
-
40289
1
-
Bit 1
Remote Off
-
40289
1
-
Bit 2
High Head Pressure 1
-
40289
1
-
Bit 3
Loss of Airflow
-
40289
1
-
Bit 5
Standby Glycol Unit On
-
40289
1
-
Bit 6
Change Filters
-
40289
1
-
Bit 8
High Temperature
-
40289
1
-
Bit 9
Low Temperature
-
40289
1
-
Bit 10
High Humidity
-
40290
1
-
Bit 0
Low Humidity
-
40290
1
-
Bit 1
Humidifier Problem
-
40290
1
-
Bit 2
Smoke Detected
-
40290
1
-
Bit 8
Loss of Water Flow
-
40290
1
-
Bit 9
Standby Unit On
-
40290
1
-
Bit 10
Short Cycle
-
40291
1
-
Bit 1
Loss of Power
-
40291
1
-
Bit 2
Local Alarm 1
- 40291 1
-
Bit 6
Local Alarm 2
-
40291
1
-
Bit 7
Local Alarm 3
-
40291
1
-
Bit 9
Local Alarm 4
-
40291
1
-
Bit 10
Vista de pagina 33