Table 28 Liebert NXL
with Liebert iCOM Single Module (SMS) - Status and Coil
Data Description
Status
Coil
Number of Bits
Notes
Input Contact 11
10379
-
1
Active on Alarm
Input Contact 12
10380
-
1
Active on Alarm
Input Contact 13
10381
-
1
Active on Alarm
Input Contact 14
10382
-
1
Active on Alarm
Input Contact 15
10383
-
1
Active on Alarm
Input Contact 16
10384
-
1
Active on Alarm
Rectifier Operation Inhibit-Ext
10385
-
1
Active on Alarm
System Fan Failure - Redundant
10386
-
1
Active on Alarm
Multiple Fan Failure
10387
-
1
Active on Alarm
Auto Restart In Progress
10388
-
1
Active on Alarm
Automatic Restart Failed
10389
-
1
Active on Alarm
Fuse Failure
10390
-
1
Active on Alarm
System Breaker(s) Open Failure
10391
-
1
Active on Alarm
System Breaker(s) Close Failure
10392
-
1
Active on Alarm
Input Filter Cycle Lock
10393
-
1
Active on Alarm
Service Code Active
10394
-
1
Active on Alarm
LBS Active
10395 - 1 Active on Alarm
LBS Inhibited
10396
-
1
Active on Alarm
Controls Reset Required
10397
-
1
Active on Alarm
Battery Test Failed
10398
-
1
Active on Alarm
Auto Restart Inhibited - Ext
10399
-
1
Active on Alarm
Battery Automatic Test Inhibited
10400
-
1
Active on Alarm
Battery Equalize
10401
-
1
Active on Alarm
Backfeed Breaker Open
10402
-
1
Active on Alarm
On Generator
10403
-
1
Active on Alarm
Power Supply Failure
10404
-
1
Active on Alarm
Battery Ground Fault
10405
-
1
Active on Alarm
Battery Charging Error
10406
-
1
Active on Alarm
System Input Power Problem
10407
-
1
Active on Alarm
System Input Current Limit
10408
-
1
Active on Alarm
Internal Communications Failure
10409
-
1
Active on Alarm
System Controller Error
10410
-
1
Active on Alarm