3B
UPS Systems
50
Table 25 Liebert Nfinity - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Number of Input Lines
30004
40004
1
-
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
-
Bits 4 - 7
Number of Output Lines
30004
40004
1
-
Bits 8 - 11
Number of Power Mod.
30010
40010
1
-
-
Number of Battery Modules Installed
30011
40011
1
-
-
Device Maximum Frame Capacity
30023
40023
2
-
-
Device System Capacity
30025
40025
2
-
VA
Nominal Input Voltage
30027
40027
1
-
V
Nominal Output Voltage
30028
40028
1
-
V
Nominal Static Bypass Switch Voltage
30029
40029
1
-
V
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
-
Nominal Battery Voltage
30034
40034
1
-
V
Auto Restart Delay
30051
40051
1
-
Seconds
Device Auto Restart Percent Setpt
30052
40052
1
-
%
Device Low Battery Time
30053
40053
1
-
Minutes
Next Battery Auto Test Time
30057
40057
1
-
Minutes
Overload Alarm Limit
30067
40067
2
-
VA
Minimum Redundant Power Modules
30074
40074
1
-
-
Load (Apparent Power)
30102
-
2
-
VA
Load (Real Power)
30104
-
2
-
W
Load / Capacity
30106
-
1
-
%
Input Frequency
30107
-
1
10
Hz
Output Frequency
30108
-
1
10
Hz
Bypass Frequency
30109
-
1
10
Hz
Battery Charge Status 30112 - 1 -
1 - 100% Charged
2 - Less than 100%
Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage
30113
-
1
-
V
Battery Time Remaining
30115
-
1
-
Minutes
Battery Charge Percentage
30116
-
1
-
%
Battery Temperature
30117
-
1
-
deg C
Transformer Temperature
30121
-
1
-
deg C
Redundant Power Modules
30124
-
1
-
-
Active Power Module Count
30126
-
1
-
-
Vista de pagina 53