Emerson Liebert FPC Manual de usuario Pagina 29

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 28
1B
Precision Cooling Products
25
Table 13 Liebert XDP with Liebert iCOM - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Supply Chilled Water Over Temp
Threshold
30413 40413 1 - deg C
Supply Chilled Water Over Temp
Threshold
30414 40414 1 - deg F
Dew Point Temperature
30415
-
1
0.1
deg C
Dew Point Temperature
30416
-
1
0.1
deg F
Auto Restart Delay
30417
40417
1
-
Seconds
System Control Mode
30418
-
1
-
0=Internal (Auto)
1=External (Manual)
Maintenance Ramp
30419
-
1
-
%
Calculated Next Maintenance
Month
30420
-
1
- -
Calculated Next Maintenance
Year
30421
-
1
- -
System On/Off Control
30422
40422
1
-
0=Off / 1=On
System Event
Acknowledge/Reset
- 40423 1
-
2=Reset
4=Acknowledge
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.