Table 22 Liebert STS
, Liebert STS/PDU
- Input and Holding Registers - STS
Controller
STS
Liebert Products
Liebert STS
Liebert STS/PDU
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Shorted SCR1
-
40289
1
-
Bit 9
Shorted SCR2
-
40289
1
-
Bit 10
Open SCR1
-
40290
1
-
Bit 0
Open SCR2
-
40290
1
-
Bit 1
Fan Failure
-
40290
1
-
Bit 2
Source 2 Overload
-
40290
1
-
Bit 3
Power Supply 2 Fault
-
40290
1
-
Bit 4
Frequency Deviation
-
40290
1
-
Bit 5
Transfer Inhibit
-
40290
1
-
Bit 6
Auto Retransfer Primed
-
40290
1
-
Bit 7
Out of Synchronization
-
40290
1
- Bit 8
Source 1 Failure
-
40290
1
-
Bit 9
Source 2 Failure
-
40290
1
-
Bit 10
Auto Retransfer Failed
-
40291
1
-
Bit 0
Overload
-
40291
1
-
Bit 1
Control Fuse 1 Blown
-
40291
1
-
Bit 2
Control Fuse 2 Blown
-
40291
1
-
Bit 3
Source 1 CB1 Open
-
40291
1
-
Bit 4
Source 2 CB2 Open
-
40291 1
-
Bit 5
Output CB3 Open
-
40291
1
-
Bit 6
Custom Alarm 1
-
40291
1
-
Bit 7
Custom Alarm 2
-
40291
1
-
Bit 8
Bypass CB4 Closed
-
40291
1
-
Bit 9
Bypass CB5 Closed
-
40291
1
- Bit 10
Custom Alarm 3
-
40292
1
-
Bit 0
Custom Alarm 4
-
40292
1
-
Bit 1
Custom Alarm 5
-
40292
1
-
Bit 2
Custom Alarm 6
-
40292
1
-
Bit 3
Custom Alarm 7
-
40292
1
-
Bit 4
Custom Alarm 8
-
40292
1
-
Bit 5
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.