Emerson Liebert FPC Manual de usuario Pagina 14

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 13
1B
Precision Cooling Products
10
Table 7 Liebert CRV - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Supply Chilled Water Over Temp
Threshold
30447 40447 1 0.1 deg F
BMS Timeout Period
30448
40448
1
-
Minutes
Auto Restart Delay
30449
40449
1
-
Seconds
Operating Efficiency
30450
-
1
-
%
Fan Speed
30451
-
1
-
%
Compressor Utilization
30452
-
1
-
%
Dehumidifier Utilization
30453
-
1
-
%
Reheat Utilization
30454
-
1
-
%
Humidifier Utilization
30455
-
1
-
%
Calculated Next Maintenance
Month
30456 - 1 - -
Calculated Next Maintenance
Year
30457 - 1 - -
Maintenance Ramp
30458
-
1
-
%
Server Class
30459 - 1 -
1=UPS
2=AIR
3=PMP
4=PDU
Air Temperature Control Sensor
30460 40460 1 -
0=Supply
1=Remote
2=Return
Remote Sensor Temperature
Calculation
30461 40461 1 -
0=Average
1=Maximum
Fan Control Mode
30462 40462 1 -
0=Internal (Auto)
1=External (Manual)
Fan Control Sensor
30463 40463 1 -
0=Supply
1=Remote
2=Return
Remote Sensor Function
Module Index 1
30464 40464 1 -
0=Disable
1=Reference
2=Control
Remote Sensor Function
Module Index 2
30465 40465 1 -
0=Disable
1=Reference
2=Control
Remote Sensor Function
Module Index 3
30466 40466 1 -
0=Disable
1=Reference
2=Control
Remote Sensor Function
Module Index 4
30467 40467 1 -
0=Disable
1=Reference
2=Control
Remote Sensor Function
Module Index 5
30468 40468 1 -
0=Disable
1=Reference
2=Control
Remote Sensor Function
Module Index 6
30469 40469 1 -
0=Disable
1=Reference
2=Control
Remote Sensor Function
Module Index 7
30470 40470 1 -
0=Disable
1=Reference
2=Control
Vista de pagina 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 99 100

Comentarios a estos manuales

Sin comentarios