2B
Power Distribution and Power Conditioning Products
42
Table 21 Liebert Datawave, Liebert FPC, Liebert PPC Precision Power Center - Input and
Holding Registers - PMP Option for Liebert FPC and Liebert PPC
Controller
Power Monitoring Panel - PMP
Option for Liebert FPC and Liebert PPC
Liebert Products
Liebert Datawave
Liebert FPC
Liebert PPC
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Liquid Detected
-
40289
1
-
Bit 9
Security Alarm
-
40289
1
-
Bit 10
Phase Rotation/Loss
-
40290
1
-
Bit 0
Datawave Overtemperature
-
40290
1
-
Bit 1
Emergency Shutdown
-
40290
1
-
Bit 2
Load On Bypass
-
40290
1
-
Bit 3
Local Alarm
-
40290
1
-
Bit 4
Custom Alarm #1
-
40290
1
-
Bit 5
Custom Alarm #2
-
40290
1
-
Bit 6
Setpoints (View)
None
-
1
-
-
Control Points (Set)
None
-
1
-
-
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.