Emerson Liebert FPC Manual de usuario Pagina 31

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 30
1B
Precision Cooling Products
27
Table 14 Liebert Challenger 3000
, Liebert Deluxe System/3
, Liebert ICS
, Liebert Himod
-
Input and Holding Registers - LAM
Controller
Advanced Microprocessor - LAM
Liebert Products
Liebert Challenger 3000
Liebert Deluxe System/3
Liebert ICS
Liebert Himod (LNA version - Using Sitescan)
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Low Humidity
-
40290
1
-
Bit 1
Humidifier Problem
-
40290
1
-
Bit 2
No Water in Humidifier Pan
-
40290
1
-
Bit 3
Compressor 1 Overload
-
40290
1
-
Bit 4
Compressor 2 Overload
-
40290
1
-
Bit 5
Main Fan Overload
-
40290
1
-
Bit 6
Manual Override
-
40290
1
-
Bit 7
Smoke Detected
-
40290
1
-
Bit 8
Loss of Water
-
40290
1
-
Bit 9
Standby Unit On
-
40290
1
-
Bit 10
Low Suction
-
40291
1
-
Bit 0
Short Cycle
-
40291
1
-
Bit 1
Loss of Power
-
40291
1
-
Bit 2
Inverter on Bypass
-
40291
1
-
Bit 3
Standby Fan On
-
40291
1
-
Bit 4
Loss of Emergency Power
-
40291
1
-
Bit 5
Local Alarm 1
-
40291
1
-
Bit 6
Local Alarm 2
-
40291
1
-
Bit 7
Off by Remote Shutdown
-
40291
1
-
Bit 8
Local Alarm 3
-
40291
1
-
Bit 9
Local Alarm 4
-
40291
1
-
Bit 10
Compressor 1 Run Hours
-
40019
1
-
-
Compressor 2 Run Hours
-
40020
1
-
-
Fan Motor Run Hours
-
40021
1
-
-
Humidifier Run Hours
-
40022
1
-
-
Setpoints (View)
Temperature Setpoint
-
40010
1
-
(R/W)
Temperature Tolerance
-
40011
1
-
(R/W)
Humidity Setpoint
-
40012
1
-
(R/W)
Humidity Tolerance
-
40013
1
-
(R/W)
High Temp Alarm Setpoint
-
40014
1
-
(R/W)
Low Temp Alarm Setpoint
-
40015
1
-
(R/W)