Vista de pagina 35
1B
Precision Cooling Products
32
Table 17 Liebert Mini-Mate 8 Ton - Input and Holding Registers - L8T
Controller
L8T
Liebert Products
Liebert Mini-Mate 8 Ton
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Status Points (View)
Temperature
-
40001
1
-
-
Humidity
-
40002
1
-
-
Cooling
-
40003
1
-
1=On / 0=Off
Heating
-
40004
1
-
1=On / 0=Off
Humidification
-
40005
1
-
1=On / 0=Off
De-humidification
-
40006
1
-
1=On / 0=Off
Econ-O-Cycle
-
40007
1
-
1=On / 0=Off
Stages
-
40008
1
-
-
% Capacity
-
40009 1
-
-
Analog input 1
-
40023 1
-
A/D raw value w/ slope
=1 and offset = 0
Analog input 2
-
40024 1
-
A/D raw value w/ slope
=1 and offset = 0
Analog input 3
-
40025 1
-
A/D raw value w/ slope
=1 and offset = 0
Analog input 4
-
40026 1
-
A/D raw value w/ slope
=1 and offset = 0
Alarm Points
Communications
-
40289
1
-
Bit 0
Local Off
-
40289
1
-
Bit 1
Remote Off
-
40289
1
-
Bit 2
High Head Pressure 1
-
40289
1
-
Bit 3
High Head Pressure 2
-
40289
1
-
Bit 4
Loss of Airflow
-
40289
1
-
Bit 5
Standby Glycol Unit On
-
40289
1
-
Bit 6
Not Used
-
40289
1
-
Bit 7
Change Filters
-
40289
1
-
Bit 8
High Temperature
-
40289
1
-
Bit 9
Low Temperature
-
40289 1
-
Bit 10
High Humidity
-
40290
1
-
Bit 0
Low Humidity
-
40290
1
-
Bit 1
Humidifier Problem
-
40290
1
-
Bit 2
Smoke Detected
-
40290
1
-
Bit 8
Loss of Water
-
40290
1
-
Bit 9
Standby Unit On
-
40290
1
-
Bit 10
Vista de pagina 35