3B
UPS Systems
86
Table 43 Liebert Series 300 UPS - Input and Holding Registers
-
Open UPS Output Switch - 40104 -
-
Delay time in Seconds, last
digit will be ignored
Reboot UPS Output Switch - 40105 1
-
Delay time in Seconds, last
digit will be ignored
Close UPS Output Switch - 40106 - -
Delay time in Seconds, last
digit will be ignored
Transfer Load to Inverter
Turn UPS Outlets On - 40112 1
-
Bitmap mask for Outlet 1-16.
All bits set to 1 will be turned
Turn UPS Outlets Off - 40113 1
-
Bitmap mask for Outlet 1-16.
All bits set to 1 will be turned
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.