3B
UPS Systems
86
Table 43 Liebert Series 300 UPS - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Output Voltage L1
30163
-
1
-
V
Output Current L1
30164
-
1
-
A
Input Voltage L2
30203
-
1
-
V
Input Current L2
30204
-
1
-
A
Bypass Voltage L2
30209
-
1
-
V
Bypass Current L2
30210
-
1
-
A
Output Voltage L2
30213
-
1
-
V
Output Current L2
30214
-
1
-
A
Input Voltage L3
30253
-
1
-
V
Input Current L3
30254
-
1
-
A
Bypass Voltage L3
30259
-
1
-
V
Bypass Current L3
30260
-
1
-
A
Output Voltage L3
30263
-
1
-
V
Output Current L3
30264
-
1
-
A
Black Out Count
30301
-
1
-
-
Brown Out Count
30302
-
1
-
-
Transient Count
30301
-
1
-
-
Silent Audible Alarm
-
40101
-
-
Any value
Battery Start
-
40102
1
-
1=Start, 0=Abort
Open UPS Output Switch - 40104 -
-
Delay time in Seconds, last
digit will be ignored
Reboot UPS Output Switch - 40105 1
-
Delay time in Seconds, last
digit will be ignored
Close UPS Output Switch - 40106 - -
Delay time in Seconds, last
digit will be ignored
Transfer Load to Bypass
-
40107
1
-
Any value
Transfer Load to Inverter
-
40108
-
Any value
Reset UPS Statistic data
-
40111
1
-
Any value
Turn UPS Outlets On - 40112 1
-
Bitmap mask for Outlet 1-16.
All bits set to 1 will be turned
On
Turn UPS Outlets Off - 40113 1
-
Bitmap mask for Outlet 1-16.
All bits set to 1 will be turned
Off
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.