3B
UPS Systems
64
Table 29 Liebert NXL with Liebert iCOM Single Module (SMS) - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Battery Temperature for Cabinet
Array Index 4
30369
-
1
-
deg C
Battery Temperature for Cabinet
Array Index 5
30370
-
1
-
deg C
Battery Temperature for Cabinet
Array Index 6
30371
-
1
-
deg C
Battery Temperature for Cabinet
Array Index 7
30372
-
1
-
deg C
Battery Temperature for Cabinet
Array Index 8
30373
-
1
-
deg C
Backfeed Breaker
30374
-
1
-
0=Open
1=Close
2=Not Installed
SBS Load Disconnect
30375
-
1
-
0=Open
1=Close
2=Not Installed
Input Breaker (CB1)
30376
-
1
-
0=Open
1=Close
2=Not Installed
Trap Filter Disconnect
30377
-
1
-
0=Open
1=Close
2=Not Installed
Output Breaker (CB2)
30378
-
1
-
0=Open
1=Close
2=Not Installed
Internal Bypass Breaker (CB3)
30379
-
1
-
0=Open
1=Close
2=Not Installed
Bypass Isolation Breaker (BIB)
30380
-
1
-
0=Open
1=Close
2=Not Installed
Rectifier Isolation Breaker (RIB)
30381
-
1
-
0=Open
1=Close
2=Not Installed
Maintenance Bypass Breaker
(MBB)
30382
-
1
-
0=Open
1=Close
2=Not Installed
Maintenance Isolation Breaker
(MIB)
30383
-
1
-
0=Open
1=Close
2=Not Installed
Output Series Static Switch
30384
-
1
-
0=Off / 1=On
2=Not Installed
Module Output Breaker (MOB)
30385
-
1
-
0=Open
1=Close
2=Not Installed
Battery Amp-Hours Consumed
30386
-
2
-
AH
Bypass Retransfer Time
Remaining
30388
-
1
-
Seconds
Inverter On/Off State
30389
-
1
-
0=Off / 1=On