3B
UPS Systems
64
Table 29 Liebert NXL with Liebert iCOM Single Module (SMS) - Input and Holding Registers
Battery Temperature for Cabinet
Array Index 4
30369
-
1
-
deg C
Battery Temperature for Cabinet
Array Index 5
30370
-
1
-
deg C
Battery Temperature for Cabinet
Array Index 6
30371
-
1
-
deg C
Battery Temperature for Cabinet
30372
-
1
-
deg C
Battery Temperature for Cabinet
Array Index 8
30373
-
1
-
deg C
Backfeed Breaker
30374
-
1
-
1=Close
SBS Load Disconnect
30375
-
1
-
1=Close
Input Breaker (CB1)
30376
-
1
-
1=Close
Trap Filter Disconnect
30377
-
1
-
1=Close
Output Breaker (CB2)
30378
-
1
-
1=Close
Internal Bypass Breaker (CB3)
30379
-
1
-
1=Close
Bypass Isolation Breaker (BIB)
30380
-
1
-
1=Close
Rectifier Isolation Breaker (RIB)
30381
-
1
-
1=Close
Maintenance Bypass Breaker
(MBB)
30382
-
1
-
1=Close
Maintenance Isolation Breaker
(MIB)
30383
-
1
-
1=Close
Output Series Static Switch
30384
-
1
-
0=Off / 1=On
2=Not Installed
Module Output Breaker (MOB)
30385
-
1
-
1=Close
Battery Amp-Hours Consumed
Bypass Retransfer Time
30388
-
1
-
Seconds