1B
Precision Cooling Products
29
Table 15 Liebert DataMate
, Liebert Mini-Mate
, Liebert Mini-Mate Plus - Input and Holding
Registers - L0B
Controller
Small Systems - L0B
Liebert Products
Liebert DataMate
Liebert Mini-Mate
Liebert Mini-Mate Plus
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Status Points (View)
Temperature
-
40001
1
-
-
Humidity
-
40002
1
-
-
Cooling
-
40003
1
-
1=On / 0=Off
Heating
-
40004
1
-
1=On / 0=Off
Humidification
-
40005
1
-
1=On / 0=Off
Dehumidification
-
40006
1
-
1=On / 0=Off
Econ-o-Cycle
-
40007
1
-
1=On / 0=Off
Stages
-
40008
1
-
-
% Capacity
-
40009
1
-
-
Alarm Points
Communications
-
40289
1
-
Bit 0
Local Off
-
40289
1
-
Bit 1
Remote Off
-
40289
1
-
Bit 2
High Temperature
-
40289
1
-
Bit 3
Low Temperature
-
40289
1
-
Bit 4
High Humidity
-
40289
1
-
Bit 5
Low Humidity
-
40289
1
-
Bit 6
Setpoints (View)
None
-
1
-
-
Control Points (Set)
Unit On/Off
-
40011
1
-
1=On / 0=Off (R/W)
Remote On/Off
- 40349 1
-
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Trendable Points (Set)
Temperature
-
1
-
-
Humidity
-
1
-
-
Reports
Trend
-
1
-
-
Status
-
1
-
-
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.