Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 96 of 149
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Bypass Not Available
40291:02
291:02
BA03_x:02
Not OK to Transfer
40291:03
291:03
BA03_x:03
Bypass Ph Rotation Error
40291:04
291:04
BA03_x:04
Manual Reset/Transfer
40291:05
291:05
BA03_x:05
Auto Re-Transfer Primed
40291:06
291:06
BA03_x:06
Overload Transfer
40291:07
291:07
BA03_x:07
Reserve Power
40291:08
291:08
BA03_x:08
Low Battery Shutdown
40291:09
291:09
BA03_x:09
DC Overvoltage Shutdown
40291:10
291:10
BA03_x:10
Battery Cycle Buffer Full
40292:00
292:00
BA04_x:00
Equipment Overtemp
40292:01
292:01
BA04_x:01
Blower/Fan Failure
40292:02
292:02
BA04_x:02
Overtemperature Shutdown
40292:03
292:03
BA04_x:03
Custom Alarm #1
40292:04
292:04
BA04_x:04
Custom Alarm #2
40292:05
292:05
BA04_x:05
Custom Alarm #3
40292:06
292:06
BA04_x:06
Custom Alarm #4
40292:07
292:07
BA04_x:07
Custom Alarm #5
40292:08
292:08
BA04_x:08
Custom Alarm #6
40292:09
292:09
BA04_x:09
Custom Alarm #7
40292:10
292:10
BA04_x:10
Custom Alarm #8
40292:00
292:00
BA05_x:00
Battery Room Overtemp
40293:01
293:01
BA05_x:01
Battery Test Running
40293:02
293:02
BA05_x:02
Auto-restart Initiated
40293:03
293:03
BA05_x:03
Auto-restart Failed
40293:04
293:04
BA05_x:04
Setpoints (View)
Overload Alarm
DC Overvoltage Alarm
Battery Discharging Alarm
Low Battery Alarm
Battery Shutdown 1 Alarm
Battery Shutdown 2 Alarm
Control Points (Set)
None