Revision B.33 2/25/2011
Liebert Monitoring Group – Development
Page 15 of 149
Liebert Environmental Units
Using Unit Control Points
This section is an example of how to utilize Liebert environmental unit Setpoints Set registers. In all cases the
Setpoints View section contains the value that the unit itself is reporting and can be used to confirm that the unit
received the transmitted command.
Example table from this document:
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Bit 0 on=unit off Bit 1 on=unit on
Multiply desired value by 1000
Multiply desired value by 1000
Bit 2 on=RH off Bit 3 on=RH on
Bit 2 on=HL off Bit 3 on=HL on
The above notes in the document refer to binary bits. Notice that register 40349 is used more than once in the table.
The table below shows the integer number in the value set from BMS column.
Reheat Lockout turns ―Off‖
Reheat Lockout turns ―On‖
Humidifier Lockout turns ―Off‖
Humidifier Lockout turns ―On‖
For the setpoint registers, the setpoint and tolerance are in the same register. Writing a zero to the field will result in
no change.
Multiply desired value by 100
Multiply desired value by 100
Some examples of valid values to send:
To make the Temperature Setpoint “70”, send a “70” to the register.
To make the Temperature Tolerance “+/- 2.5 degrees”, send “2500” to the register.
To make the Temperature Tolerance “+/- 2.5 degrees” and Setpoint “70”, send “2570” to the register.
To make the Humidity Setpoint “50%”, send a “50” to the register.
To make the Humidity Tolerance “+/- 5%”, send “5000” to the register.
To make the Humidity Tolerance “+/- 5%” and Setpoint “50%”, send “5050” to the register.