Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 15 of 149
Liebert Environmental Units
Using Unit Control Points
This section is an example of how to utilize Liebert environmental unit Setpoints Set registers. In all cases the
Setpoints View section contains the value that the unit itself is reporting and can be used to confirm that the unit
received the transmitted command.
Example table from this document:
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Control Points (Set)
Unit On/Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Reheat Lockout
40349
349
BC01_x
Bit 2 on=RH off Bit 3 on=RH on
Humidifier Lockout
40349
349
BC01_x
Bit 2 on=HL off Bit 3 on=HL on
The above notes in the document refer to binary bits. Notice that register 40349 is used more than once in the table.
The table below shows the integer number in the value set from BMS column.
Function
Command if
BIT=1
BIT
Number
Value sent from
BMS
Resulting Action
Unit On/Off
―Off‖
BIT 0
1
Units turns ―Off‖
Unit On/Off
―On‖
BIT 1
2
Unit turns ―On‖
Reheat Lockout
―Off‖
BIT 2
4
Reheat Lockout turns ―Off‖
Reheat Lockout
―On‖
BIT 3
8
Reheat Lockout turns ―On‖
Humidifier Lockout
―Off‖
BIT 4
16
Humidifier Lockout turns ―Off‖
Humidifier Lockout
―On‖
BIT 5
32
Humidifier Lockout turns ―On‖
For the setpoint registers, the setpoint and tolerance are in the same register. Writing a zero to the field will result in
no change.
Control Points (Set)
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 100
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 100
Some examples of valid values to send:
To make the Temperature Setpoint “70”, send a “70” to the register.
To make the Temperature Tolerance “+/- 2.5 degrees”, send “2500” to the register.
To make the Temperature Tolerance “+/- 2.5 degrees” and Setpoint “70”, send “2570” to the register.
To make the Humidity Setpoint “50%”, send a “50” to the register.
To make the Humidity Tolerance “+/- 5%”, send “5000” to the register.
To make the Humidity Tolerance “+/- 5%” and Setpoint “50%”, send “5050” to the register.