Liebert Monitoring Group Development
Page 144 of 149
Water/Liquid Detection Unit LDS5000 WD5
Hardware Compatibility
Liebert Units:
LDS5000
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Installed Cable Footage 1
40001
1
BS01_x
Installed Cable Footage 2
40002
2
BS02_x
Not Used Spare
40003
3
BS03_x
Not Used Spare
40004
4
BS04_x
Leak Det Footage Cable 1
40005
5
BS05_x
Leak Det Footage Cable 2
40006
6
BS06_x
Not Used Spare
40007
7
BS07_x
Not Used Spare
40008
8
BS08_x
Leakage Current Cable 1
40009
9
BS09_x
Leakage Current Cable 2
40010
10
BS10_x
Not Used Spare
40011
11
BS11_x
Not Used Spare
40012
12
BS12_x
Feet / Meters
40013
13
BS13_x
Alarm Points
Communications
40289:00
289:0
BA01_x:00
Leak Detected Cable 1
40289:01
289:1
BA01_x:01
Cable Fault Cable 1
40289:02
289:2
BA01_x:02
Leak Detected Cable 2
40289:03
289:3
BA01_x:03
Cable Fault Cable 2
40289:04
289:4
BA01_x:04
Not Used Spare
40289:05
289:5
BA01_x:05
Not Used Spare
40289:06
289:6
BA01_x:06
Not Used Spare
40289:07
289:7
BA01_x:07
Not Used Spare
40289:08
289:8
BA01_x:08
Setpoints (View)
None
Control Points (Set)
Alarm Silence
Alarm Reset
Vista de pagina 143