Emerson Autochangeover Controllers AC8 Manual de usuario Pagina 128

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 149
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 127
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 128 of 149
UPS Unit GXT PGX
Hardware Compatibility
Liebert Units:
GXT
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
UPS Load VA
40001
BS01_x
UPS Load Watt
40002
BS02_x
UPS Load Percent
40003
BS03_x
Input Frequency
40004
BS04_x
Scale By 10
Output Frequency
40005
BS05_x
Scale By 10
Bypass Frequency
40006
BS06_x
Scale By 10
Load On Inverter
UPS Load On Bypass
Battery Test Result
DC-DC Status
Inverter Ready Status
Power Factor Correction Stat
Battery Charge Comp Status
Replace Battery Status
Battery Test In Progress
Battery Charge Status
Battery Voltage
40007
BS07_x
Battery Charge Percentage
40008
BS08_x
Battery Deplete Time
40009
BS09_x
Ambient Temperature
Input Voltage Vab
40010
BS10_x
Input Voltage Van
40011
BS11_x
Bypass Voltage Vab
40012
BS12_x
Bypass Voltage Van
40013
BS13_x
Output Voltage Vab
40014
BS14_x
Output Voltage Van
40015
BS15_x
Output Current Ia
40016
BS16_x
Output Load % Phase A
40017
BS17_x
Vista de pagina 127