Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 33 of 149
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Cool 2 Operating Mode (Days)
Cool 2 Operating Mode (Hours)
Fan Operation (Days)
Fan Operation (Hours)
Heat 1Operating Mode (Days)
Heat 1Operating Mode (Hours)
Heat 2 Operating Mode (Days)
Heat 2 Operating Mode (Hours)
Humidify Operating Mode (Days)
Humidity Operating Mode (Hours)
Cool Service (Days)
Cool Service (Hours)
Filter Service (Days)
Filter Service (Hours)
Humidifier Service (Days)
Humidifier Service (Hours)
Temperature Control Status
40019
19
BS19_x
Battery Voltage Level
40020
20
BS20_x
Remote Shutdown Status
40021
21
BS21_x
General Alarm Status
40022
22
BS22_x
Audible Alarm Status
40023
23
BS23_x
Temperature Control Select
40024
24
BS24_x
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Faulty Sensor
40289:01
289:01
BA01_x:01
High Temperature
40289:02
289:02
BA01_x:02
Low Temperature
40289:03
289:03
BA01_x:03
High Humidity
40289:04
289:04
BA01_x:04
Low Humidity
40289:05
289:05
BA01_x:05
Loss of Airflow
40289:06
289:06
BA01_x:06
Water Under Floor
40289:07
289:07
BA01_x:07
Cool 1 Low Pressure Alarm
40289:08
289:08
BA01_x:08
Cool 2 Low Pressure Alarm
40289:09
289:09
BA01_x:09
Cool 1 High Pressure Alarm
40289:10
289:10
BA01_x:10
Cool 2 High Pressure Alarm
40290:00
290:00
BA02_x:00
Cool Service
40290:01
290:01
BA02_x:01
Humidifier Service
40290:02
290:02
BA02_x:02