Power Unit Voltage-Current-Freq. Monitor Panel VCF
Hardware Compatibility
Liebert Units:
MPU4000, Datawave, Precision Power Center
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Voltage Out X-Y
40001
1
BS01_x
Voltage Out Y-Z
40002
2
BS02_x
Voltage Out Z-X
40003
3
BS03_x
Voltage Out X-N
40004
4
BS04_x
Voltage Out Y-N
40005
5
BS05_x
Voltage Out Z-N
40006
6
BS06_x
Current Out A
40007
7
BS07_x
Current Out B
40008
8
BS08_x
Current Out C
40009
9
BS09_x
Ground Current
40010
10
BS10_x
Neutral Current
40011
11
BS11_x
KVA
40012
12
BS12_x
Frequency
40013
13
BS13_x
Divide by 10 for correct value
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Output Undervoltage
40289:1
289:1
BA01_x:01
Output Overvoltage
40289:2
289:2
BA01_x:02
Transformer Overtemp
40289:3
289:3
BA01_x:03
Local Alarm #1
40289:4
289:4
BA01_x:04
Local Alarm #2
40289:5
289:5
BA01_x:05
Setpoints (View)
None
Control Points (Set)
None