UPS Unit Single Module SICE 7200 & HiPulse UPS SSM
Hardware Compatibility
Liebert Units:
SICE 7200
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Output Voltage L1-L2
40001
1
BS01_x
Output Voltage L2-L3
40002
2
BS02_x
Output Voltage L3-L1
40003
3
BS03_x
Output Voltage L1-N
Output Voltage L2-N
Output Voltage L3-N
Output Amps L1
40004
4
BS04_x
Output Amps L2
40005
5
BS05_x
Output Amps L3
40006
6
BS06_x
Output Amps Neutral
Power L1
40007
7
BS07_x
Power L2
40008
8
BS08_x
Power L3
40009
9
BS09_x
Bypass Frequency
40010
10
BS10_x
Divide by 10 for correct value
Inverter Frequency
40011
11
BS11_x
Divide by 10 for correct value
Input Voltage L1-L2
Input Voltage L2-L3
Input Voltage L3-L1
Battery Voltage
40012
12
BS12_x
Battery Amperage
40013
13
BS13_x
Apparent Power L1
40014
14
BS14_x
Apparent Power L2
40015
15
BS15_x
Apparent Power L3
40016
16
BS16_x
% Load L1
40017
17
BS17_x
% Load L2
40018
18
BS18_x
% Load L3
40019
19
BS19_x
%Battery Charge
40020
20
BS20_x