Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 58 of 149
Air Unit XDP Refrigerant Pumping Unit XDP W/ iCOM Control
Hardware Compatibility
Liebert Units:
XDP Unit w/ iCOM Control
SiteScan Interface Modules:
SiteLink-E (Exec. B Modules)
SiteScan Availability
Modbus
Register
BACnet
Instance
Notes:
Status Points (View)
Valve % Open
40001
BS01_x
Pump 1 Status
40002
BS02_x
1=On / 0=Off
Pump 2 Status
40003
BS03_x
1=On / 0=Off
Supply Temperature
40004
BS04_x
Divide by 10 for correct value
Chilled Water Temperature
40005
BS05_x
Divide by 10 for correct value
Unit Status
40006
BS06_x
Off:1=Rmt, 3=Lcl, 4=Restart, 5=Epo; On=2
Scale F or C
40007
BS07_x
43=C / 46=F
Sensor A Temperature
40008
BS08_x
Sensor A Humidity
40009
BS09_x
Sensor A Dewpoint
40010
BS10_x
Sensor B Temperature
40011
BS11_x
Sensor B Humidity
40012
BS12_x
Sensor B Dewpoint
40013
BS13_x
Run Hours (View)
Pump 1 Run Hours
40014
BS14_x
Pump 2 Run Hours
40015
BS15_x
Setpoints (View)
Temperature Setpoint
40016
BS16_x
High Temp Alarm Setpoint
40017
BS17_x
Low Temp Alarm Setpoint
40018
BS18_x
Dewpoint Alarm Setpoint
40019
BS19_x
Refrigerant Temp Alarm Setpoint
40020
BS20_x
Chilled Water Temp Alarm Setpoint
40021
BS21_x
Dewpoint Margin Setpoint
40022
BS22_x
Temperature Scale F or C
0=F 1=C
Auto-restart Delay Setpoint
40023
BS23_x
Unit Status
1=On / 0=Off
Maintenance Mode Status
40024
BS24_x
On=All alarms disabled
Setpoints (Set)
Temperature Setpoint
40350
BC02_x
High Temp Alarm Setpoint
Low Temp Alarm Setpoint
Dewpoint Alarm Setpoint
40351
BC02_x