Emerson Autochangeover Controllers AC8 Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 149
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 17 of 149
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
Control Points (Set)
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Trendable points (Set)
Temperature
Humidity
Reports
Trend
Status