Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 95 of 149
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Bypass Frequency
Total Operating Hours
Module Number
Total # Battery Discharge
Accumulated Battery Time
Accumulated Battery
Amp/Hr
Accumulated Battery kW/Hr
Battery Charge Percent
Battery Time Remaining
Battery Temperature
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Output Undervoltage
40289:01
289:01
BA01_x:01
Output Overvoltage
40289:02
289:02
BA01_x:02
Battery Discharge
40289:03
289:03
BA01_x:03
Frequency Deviation
40289:04
289:04
BA01_x:04
Input Failure
40289:05
289:05
BA01_x:05
Hardware Shutdown
40289:06
289:06
BA01_x:06
DC Ground Fault
40289:07
289:07
BA01_x:07
Input CB Open
40289:08
289:08
BA01_x:08
Bypass CB Closed
40289:09
289:09
BA01_x:09
Output CB Open
40289:10
289:10
BA01_x:10
Static Switch Disconnected
40290:00
290:00
BA02_x:00
DC Cap Fuse Blown
40290:01
290:01
BA02_x:01
Low Battery Reserve
40290:02
290:02
BA02_x:02
Output Overload
40290:03
290:03
BA02_x:03
Rectifier Fuse Blown
40290:04
290:04
BA02_x:04
Emergency Power Off
40290:05
290:05
BA02_x:05
Ambient Overtemperature
40290:06
290:06
BA02_x:06
Load On Bypass
40290:07
290:07
BA02_x:07
Static Switch Disabled
40290:08
290:08
BA02_x:08
Battery Disconnected
40290:09
290:09
BA02_x:09
Control Power Failure
40290:10
290:10
BA02_x:10
Inverter Fault
40291:00
291:00
BA03_x:01
Input Current Unbalanced
40291:01
291:01
BA03_x:02