Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 51 of 149
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Setpoints (View)
Humidity Setpoint
40019
BS19
Humd Proportional Band
40020
BS20
Humd Deadband
Autorestart Delay
IR Humidifier Flush Rate
High Temperature Alarm
40021
BS21
Low Temperature Alarm
40022
BS22
High Humidity Alarm
40023
BS23
Low Humidity Alarm
40024
BS24
Setpoints (Set)
Temperature Setpoint
40350
BC02_1
Temp Proportional Band
40350
BC02_2
Scale by 1000 (e.g. 2=2000 Modbus Only)
Temp Deadband
Humidity Setpoint
40351
BC03_1
Humd Proportional Band
40351
BC03_2
Scale by 1000 (e.g. 5=5000 Modbus Only)
Humd Deadband
Autorestart Delay
IR Humidifier Flush Rate
High Temperature Alarm
Low Temperature Alarm
High Humidity Alarm
Low Humidity Alarm
Commands (Set)
Unit On/Off
40349:0,1
BC01_1
Bit pair 0,1;1=off, 2=on (Modbus Only)
Humidifier Lockout
40349:2,3
BC01_2
Bit pair 2,3; 1=normal, 2=lckout (Modbus Only)
Reheat Lockout
40349:4,5
BC01_3
Bit pair 4,5; 1=normal, 2=lckout (Modbus Only)
Alarms
Discrete BACnet alarm objects available use auto-
discover for this unit
Loss Of Comm
40289:0
BA01_x:0
Main Fan Overload
40289:1
BA01_x:1
Loss of Airflow
40289:2
BA01_x:2
Loss of Water Flow
40289:3
BA01_x:3
Compressor 1 High Pressure
40289:4
BA01_x:4
Compressor 1 Overload
40289:5
BA01_x:5
Compressor 2 High Pressure
40289:6
BA01_x:6
Compressor 2 Overload
40289:7
BA01_x:7
Smoke Detected
40289:8
BA01_x:8
Water Detected
40289:9
BA01_x:9