Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 124 of 149
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Loss Of Communications
40289:00
BA01_x:00
Load On Battery
40289:01
BA01_x:01
Reserved
40289:02
BA01_x:02
Load On Bypass Permanent
40289:03
BA01_x:03
UPS Overload
40289:04
BA01_x:04
Battery Shutdown imminent
40289:05
BA01_x:05
Inverter Not Sync
40289:06
BA01_x:06
Input Power Failure
40289:07
BA01_x:07
Bypass SBS SCR Open fault
40289:08
BA01_x:08
Bypass Input Fault
40289:09
BA01_x:09
Setpoints (View)
Device Type
UPS Sub Module Number
UPS Battery Count
UPS Outlet Circuitry Supported
UPS Type Is Offline
UPS Type Is Interactive
UPS Has Dual Inputs
40024
BS24_x
Setpoints (Set)
None
Trend Points
Load VA
Load Watts
Input Current A
Input Current B
Input Current C
Output Current A
Output Current B
Output Current C