Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 50 of 149
Air Unit iCOM DS & Retrofit (2mb version SiteLink)
Hardware Compatibility
Liebert Units:
iCOM DS controls and iCOM retrofit using Optional IS485 interface card
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Unit On/Off Status
40001
BS01
Unit Standy Status
40002
BS02
Control Mode (Auto, Manual)
Control Reason
Fan Status
Cooling Status
40003
BS03
Freecooling Status
Hot Water State
Electric Heater State
40004
BS04
Humidifier State
40005
BS05
De-humidifier State
40006
BS06
Audible Alarm State
Cooling Ramp
40007
BS07
Heating Ramp
40008
BS08
Return Temp
40009
BS09
Return Humidity
40010
BS10
Run Hours (View)
Conditioner Run Hrs.
40011
BS11
Comp 1 Run Hrs.
40012
BS12
Comp 2 Run Hrs.
40013
BS13
Humidifier Run Hrs.
40014
BS14
Reheat 1 Run Hrs.
Reheat 2 Run Hrs.
Reheat 3 Run Hrs.
Setpoints (View)
Front Display Temp Scale
Humidifier Lockout Status
40015
BS15
Reheat Lockout Status
40016
BS16
Temperature Setpoint
40017
BS17
Temp Proportional Band
40018
BS18
Temp Deadband