Emerson Autochangeover Controllers AC8 Manual de usuario Pagina 93

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 149
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 92
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 93 of 149
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Control Power Failure
40290:00
290:00
BA02_x:00
Overload Shutdown
40290:01
290:01
BA02_x:01
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current Out A
Current Out B
Current Out C
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
DC Bus Voltage
DC Bus Current
KW
KVA
Reports
Trend
Status