Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 45 of 149
Air Unit X-Treme Density Coolant Pumping Unit XDP
Hardware Compatibility
Liebert Units:
X-Treme Density Coolant Pumping Unit
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Valve % Open
40001
1
BS01_x
Pump 1 Status
40002
2
BS02_x
1=On / 0=Off
Pump 2 Status
40003
3
BS03_x
1=On / 0=Off
Fluid Temperature
40004
4
BS04_x
Divide by 10 for correct value
Chilled Water Temperature
40005
5
BS05_x
Divide by 10 for correct value
Unit Status
40006
6
BS06_x
1=On / 0=Off
Scale F or C
40007
7
BS07_x
43=C / 46=F
Local Temperature
40008
8
BS08_x
Local Humidity
40009
9
BS09_x
Local Dewpoint
40010
10
BS10_x
Remote Temperature
40011
11
BS11_x
Remote Humidity
40012
12
BS12_x
Remote Dewpoint
40013
13
BS13_x
Alarm Points
Communications
40289:00
289:0
BA01_x:00
Local Off
40289:01
289:1
BA01_x:01
Remote Off
40289:02
289:2
BA01_x:02
Loss Of Flow P1
40289:03
289:3
BA01_x:03
Loss Of Flow P2
40289:04
289:4
BA01_x:04
Pump Short Cycle
40289:05
289:5
BA01_x:05
Condensation
40289:06
289:6
BA01_x:06
Refrigerant Leak
40289:07
289:7
BA01_x:07
Valve Failure
40289:08
289:8
BA01_x:08
Customer Alarm 1
40289:09
289:9
BA01_x:09
Fan Failure Alarm
40289:10
289:10
BA01_x:10
High Chilled Water Temp
40290:00
290:0
BA02_x:00
Low Chilled Water Temp
40290:01
290:1
BA02_x:01
Failed Chilled Water Sensor
40290:02
290:2
BA02_x:02
High Remote Temp
40290:03
290:3
BA02_x:03
Low Remote Temp
40290:04
290:4
BA02_x:04