Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 47 of 149
Air Unit X-Treme Density Chiller Unit XDC
Hardware Compatibility
Liebert Units:
X-Treme Density Chiller Unit
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Pump 1 Status
40001
N/A
BS01_x
1=On / 0=Off
Pump 2 Status
40002
N/A
BS02_x
1=On / 0=Off
Cooling %
40003
N/A
BS03_x
Compressor 1A status
40004
N/A
BS04_x
1=On / 0=Off
Compressor 1B status
40005
N/A
BS05_x
1=On / 0=Off
HG Valve1 %
40006
N/A
BS06_x
Compressor 2A status
40007
N/A
BS07_x
1=On / 0=Off
Compressor 2B status
40008
N/A
BS08_x
1=On / 0=Off
HG Valve2 %
40009
N/A
BS09_x
Refer Temp 1
40010
N/A
BS10_x
Divide by 10 for correct value
Refer Temp 2
40011
N/A
BS11_x
Divide by 10 for correct value
CW Temp
40012
N/A
BS12_x
Divide by 10 for correct value
Unit Status
40013
N/A
BS13_x
1=On / 0=Off
Scale F or C
40014
N/A
BS14_x
43=C / 46=F
Local Temp
40015
N/A
BS15_x
Local Humidity
40016
N/A
BS16_x
Local Dew Point
40017
N/A
BS17_x
Remote Temp
40018
N/A
BS18_x
Remote Humidity
40019
N/A
BS19_x
Remote Dew Point
40020
N/A
BS20_x
Alarm Points
Communications
40289:00
N/A
BA01_x:00
Local Off
40289:01
N/A
BA01_x:01
Remote Off
40289:02
N/A
BA01_x:02
Loss Of Flow Pump 1
40289:03
N/A
BA01_x:03
Loss Of Flow Pump 2
40289:04
N/A
BA01_x:04
Pump Short Cycle
40289:05
N/A
BA01_x:05
Customer Alarm 1
40289:06
N/A
BA01_x:06
Condensation
40289:07
N/A
BA01_x:07
Fan Failure Alarm
40289:08
N/A
BA01_x:08