Emerson Autochangeover Controllers AC8 Manual de usuario Pagina 114

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 149
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 113
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 114 of 149
UPS Unit Single Module Series AP301/302 SM3
Hardware Compatibility
Liebert Units:
Single Module UPS AP301/302
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Bypass Voltage A-N
40016
16
BS16_x
Bypass Voltage B-N
40017
17
BS17_x
Bypass Voltage C-N
40018
18
BS18_x
Voltage in A-N
40001
1
BS01_x
Voltage in B-N
40002
2
BS02_x
Voltage in C-N
40003
3
BS03_x
Voltage Out A-N
40004
4
BS04_x
Voltage Out B-N
40005
5
BS05_x
Voltage Out C-N
40006
6
BS06_x
Current In A
Current In B
Current In C
Current Out A
40007
7
BS07_x
Current Out B
40008
8
BS08_x
Current Out C
40009
9
BS09_x
% Capacity
40015
15
BS15_x
DC Bus Voltage
40010
10
BS10_x
DC Bus Current
40011
11
BS11_x
kVA
40012
12
BS12_x
kW
40013
13
BS13_x
Input Frequency
Divide by 10 for correct value
Bypass Frequency
Divide by 10 for correct value
Output Frequency
40014
14
BS14_x
Divide by 10 for correct value
Modbus Only
Last Battery Test Status
40022
22
BS22_x
0=failed / 1= passed
Inverter Status
40023
23
BS23_x
0=off / 1=on
Model Number
40020
20
BS20_x
KVA Size
40019
19
BS19_x
Vista de pagina 113
1 2 ... 109 110 111 112 113 114 115 116 117 118 119 ... 148 149

Comentarios a estos manuales