Emerson Autochangeover Controllers AC8 Manual de usuario Pagina 63

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 149
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 62
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 63 of 149
Power Unit Power Monitoring Panel PMP
Hardware Compatibility
Liebert Units:
Datawave, Precision Power Center
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Voltage In A-B
40001
1
BS01_x
Voltage In B-C
40002
2
BS02_x
Voltage In C-A
40003
3
BS03_x
Voltage Out A-B
40004
4
BS04_x
Voltage Out B-C
40005
5
BS05_x
Voltage Out C-A
40006
6
BS06_x
Voltage Out A-N
40007
7
BS07_x
Voltage Out B-N
40008
8
BS08_x
Voltage Out C-N
40009
9
BS09_x
Current Out A
40010
10
BS10_x
Current Out B
40011
11
BS11_x
Current Out C
40012
12
BS12_x
Ground Current
40013
13
BS13_x
Divide by 10 for correct value
Neutral Current
40014
14
BS14_x
KVA
40015
15
BS15_x
KW
40016
16
BS16_x
Frequency
40017
17
BS17_x
Divide by 10 for correct value
% Capacity A
40018
18
BS18_x
% Capacity B
40019
19
BS19_x
% Capacity C
40020
20
BS20_x
Alarm Points
Discrete BACnet alarm objects available
use auto-discover for this unit
Communications
40289:00
289:00
BA01_x:00
Output Undervoltage
40289:01
289:01
BA01_x:01
Output Overvoltage
40289:02
289:02
BA01_x:02
Output Overcurrent
40289:03
289:03
BA01_x:03
Frequency Deviation
40289:04
289:04
BA01_x:04
Vista de pagina 62